Fire Sprinkler Repair

Sprinkler System Service & Repair

Proudly serving the Puget Sound

1534 First Ave. South
Seattle, WA 98134

   206.232.8569             206.340.6100

LIC. #COLUMFI952MG
LOCAL 699 Contractor

Columbia Fire Sprinkler System Service & Repair
fire sprinkler systems
Fire Sprinkler Systems Services

  FAQ´s  

For your convenience we would like to provide some answers to some frequently asked questions. Feel free to send us your own question, we will do our best to provide you with an answer.

General Fire Sprinkler Systems Inspection, Testing, Maintenance and Repair
Q: What is a Wet pipe system?

A: By a wide margin, wet pipe sprinkler systems are installed more often than all other types of fire sprinkler systems. They also are the most reliable, because they are simple, with the only operating components being the automatic sprinklers and (commonly, but not always) the automatic alarm check valve. An automatic water supply provides water under pressure to the system piping.

Operation - When an automatic sprinkler is exposed for a sufficient time to a temperature at or above the temperature rating, the heat sensitive element (glass bulb or fusible link) releases, allowing water to flow from that sprinkler.


General Fire Sprinkler Systems Inspection, Testing, Maintenance and Repair
Q: What is a Dry pipe system

A: Dry pipe systems are installed in spaces in which the ambient temperature may be cold enough to freeze the water in a wet pipe system, rendering the system inoperable. Dry pipe systems are most often used in unheated buildings, in parking garages, in outside canopies attached to heated buildings (in which a wet pipe system would be provided), or in refrigerated coolers. Dry pipe systems are the second most common sprinkler system type. In regions using NFPA regulations, dry pipe systems cannot be installed unless the range of ambient temperatures reaches below 40F.

Operation - Water is not present in the piping until the system operates. The piping is filled with air below the water supply pressure. To prevent the larger water supply pressure from forcing water into the piping, the design of the dry pipe valve (a specialized type of check valve) results in a greater force on top of the check valve clapper by the use of a larger valve clapper area exposed to the piping air pressure, as compared to the higher water pressure but smaller clapper surface area.

When one or more of the automatic sprinklers is exposed to for a sufficient time to a temperature at or above temperature rating, it opens, allowing the air in the piping to vent from that sprinkler. Each sprinkler operates individually. As the air pressure in the piping drops, the pressure differential across the dry pipe valve changes, allowing water to enter the piping system. Water flow from sprinklers needed to control the fire is delayed until the air is vented from the sprinklers. For this reason, dry pipe systems are usually not as effective as wet pipe systems in fire control during the initial stages of the fire.

Some view dry pipe sprinklers as advantageous for protection of collections and other water sensitive areas. This perceived benefit is due to a fear that wet system piping may leak, while dry pipe systems will not. However, the same potential for accidental water damage exists, as dry pipe systems will only provide a slight delay prior to water discharge while the air in the piping is released from the pipe.


General Fire Sprinkler Systems Inspection, Testing, Maintenance and Repair
Q: What is a Deluge system

A: "Deluge" systems are systems in which all sprinklers connected to the water piping system are open, in that the heat sensing operating element is removed, or specifically designed as such. These systems are used for special hazards where rapid fire spread is a concern, as they provide a simultaneous application of water over the entire hazard. They are sometimes installed in personnel egress paths or building openings to slow travel of fire (e.g., openings in a fire-rated wall).

Water is not present in the piping until the system operates. Because the sprinkler orifices are open, the piping is at atmospheric pressure. To prevent the water supply pressure from forcing water into the piping, a deluge valve is used in the water supply connection, which is a mechanically latched valve. It is a non-resetting valve, and stays open once tripped.

Because the heat sensing elements present in the automatic sprinklers have been removed (resulting in open sprinklers), the deluge valve must be opened as signaled by a fire alarm system. The type of fire alarm initiating device is selected mainly based on the hazard (e.g., smoke detectors, heat detectors, or optical flame detectors). The initiation device signals the fire alarm panel, which in turn signals the deluge valve to open. Activation can also be manual, depending on the system goals. Manual activation is usually via an electric or pneumatic fire alarm pull station, which signals the fire alarm panel, which in turn signals the deluge valve to open.

Operation - Activation of a fire alarm initiating device, or a manual pull station, signals the fire alarm panel, which in turn signals the deluge valve to open, allowing water to enter the piping system. Water flows from all sprinklers simultaneously.


General Fire Sprinkler Systems Inspection, Testing, Maintenance and Repair
Q: What is a Pre-Action system

A: Pre-action sprinkler systems are specialized for use in locations where accidental activation is undesired, such as in museums with rare art works, manuscripts, or books; and Data Centers, for protection of computer equipment from accidental water discharge.

Pre-action systems are hybrids of wet, dry, and deluge systems, depending on the exact system goal. There are two main sub-types of pre-action systems: single interlock, and double interlock.

The operation of single interlock systems are similar to dry systems except that these systems require that a “preceding” fire detection event, typically the activation of a heat or smoke detector, takes place prior to the “action” of water introduction into the system’s piping by opening the pre-action valve, which is a mechanically latched valve (i.e., similar to a deluge valve). In this way, the system is essentially converted from a dry system into a wet system. The intent is to reduce the undesirable time delay of water delivery to sprinklers that is inherent in dry systems. Prior to fire detection, if the sprinkler operates, or the piping system develops a leak, loss of air pressure in the piping will activate a trouble alarm. In this case, the pre-action valve will not open due to loss of supervisory pressure, and water will not enter the piping.

The operation of double interlock systems are similar to deluge systems except that automatic sprinklers are used. These systems require that both a “preceding” fire detection event, typically the activation of a heat or smoke detector, and an automatic sprinkler operation take place prior to the “action” of water introduction into the system’s piping. Activation of either the fire detectors alone, or sprinklers alone, without the concurrent operation of the other, will not allow water to enter the piping. Because water does not enter the piping until a sprinkler operates, double interlock systems are considered as dry systems in terms of water delivery times, and similarly require a larger design area.


General Fire Sprinkler Systems Inspection, Testing, Maintenance and Repair
Q: What is a Foam Water Sprinkler system

A: A foam water fire sprinkler system is a special application system, discharging a mixture of water and low expansion foam concentrate, resulting in a foam spray from the sprinkler. These systems are usually used with special hazards occupancies associated with high challenge fires, such as flammable liquids, and airport hangars. Operation is as described above, depending on the system type into which the foam is injected.


Q: What is a Water Spray system

A: "Water Spray" systems are operationally identical to a deluge system, but the piping and discharge nozzle spray patterns are designed to protect a uniquely configured hazard, usually being three dimensional components or equipment (i.e., as opposed to a deluge system, which is designed to cover the horizontal floor area of a room). The nozzles used may not be listed fire sprinklers, and are usually selected for a specific spray pattern to conform to the three dimensional nature of the hazard (e.g., typical spray patterns being oval, fan, full circle, narrow jet). Examples of hazards protected by water spray systems are electrical transformers containing oil for cooling or turbine generator bearings. Water spray systems can also be used externally on the surfaces of tanks containing flammable liquids or gases (such as hydrogen). Here the water spray is intended to cool the tank and its contents to prevent tank rupture/explosion (BLEVE) and fire spread.

© 2010 Columbia Fire . All rights reserved.

Columbia Fire, Inc.
1534 First Ave. South
Seattle, WA 98134

Office: 206. 232.8569
(Available 24 hours for Emergencies)
Fax: 206.340.6100

Email: marty@columbiafire.net

site map   |   privacy policy

Bellevue Website Design by The Image Dept.

Our Fire Sprinkler Services include:

  • Wet Pipe Fire Sprinkler Systems
  • Dry Pipe Fire Sprinkler Systems
  • Deluge Fire Sprinkler Systems
  • Pre-action Fire Sprinkler Systems
  • Deluge system
  • Control Valves
  • Functional test of all systems
  • Priming level
  • Check Anti-Freeze
  • Low pressure alarm
  • Tanks
  • Fire Pump Service and Install
  • Flow alarm
  • Main drain test
  • Check static pressure
  • Check residual pressure
  • Preaction system
  • Check control valves
  • Components
  • Wet pipe system flow
  • Check name plates
  • Dry pipe system
  • Spare sprinkler heads
  • Check all special Systems
  • Water supply

We provide Fire Sprinkler Service and Repair for:

Allyn, Arlington, Auburn, Bangor, Belfair, Bellevue, Bonney Lake, Bremerton, Brownsville, Burley, Chico, Clinton, Coupeville, Des Moines, Edmonds, Everett, Federal Way, Fox Island, Freeland, Gig Harbor, Gorst, Graham, Grapeview, Greenbank, Hansville, Holly, Indianola, Issaquah, Kent, Key Center, Keyport, Kingston, Kirkland, Lake Stevens, Langley, Little Boston, Lynnwood, Manchester, Marysville, Mill Creek, Mukilteo, Navy Yard City, Oak Harbor, Olalla, Olympia, Orting, Port Gamble, Port Orchard, Poulsbo, Purdy, Puyallup, Redmond, Renton, Seabeck, SeaTac, Seattle, Silverdale, Snohomish, South Colby, Southworth, Steilacoom, Suquamish, Tacoma, Tahuya, Tracyton, Tukwila, Tumwater, Yelm